| Rated voltage | Commonly 12 kV, 17.5 kV, 24 kV or 36 kV | Provides insulation and switching capability suitable for medium-voltage distribution systems. | Confirm that the rated voltage is equal to or higher than the highest system operating voltage. |
| Short-circuit breaking current | 16 kA, 20 kA or 25 kA rms symmetrical, typically for 1 second | Allows the circuit breaker or fuse-switch combination to interrupt prospective fault current without unsafe loss of function. | Match the equipment rating with the calculated prospective short-circuit current at the installation point. |
| Short-time withstand current | 16–25 kA for 1 second is a common medium-voltage design range | Withstands thermal and electrodynamic forces while upstream protection clears a fault. | Check both the rms value and the specified duration; a higher peak withstand rating may also be required. |
| Peak withstand current | Often approximately 2.5 times the rated short-time withstand current at 50 Hz | Limits mechanical damage caused by the first high-current asymmetrical peak of a short circuit. | Use the exact manufacturer declaration and applicable standard value rather than estimating for final design. |
| Switching technology | Vacuum circuit breaker or load-break switch with current-limiting fuses | Vacuum interruption reduces arc duration in the interrupter; properly coordinated fuses can limit fault energy. | Verify interrupting capacity, making capacity, duty-cycle rating and protection coordination. |
| Earthing switch | Fault-making earthing switch where specified; short-time withstand aligned with the assembly rating | Provides a controlled discharge path and supports safe maintenance after isolation. | Confirm making capacity, interlocking arrangement and the earthing switch position indication. |
| Mechanical interlocking | Prevents unsafe sequences such as closing the earthing switch onto an energized circuit | Reduces operator error during switching, isolation and maintenance procedures. | Test all permitted and prohibited operating sequences during commissioning. |
| Key or electrical interlocking | Optional trapped-key, solenoid or control-circuit interlocking | Adds procedural control between cable compartments, bus sections, circuit breakers and earthing points. | Ensure the interlock logic reflects the site operating procedure and emergency bypass policy. |
| Internal arc classification | IAC AFL, AFLR or another declared classification under IEC 62271-200 | Helps protect personnel from hot gases, pressure and ejected parts during an internal arc event. | Check the tested current, test duration, accessibility sides and installation conditions; IAC is not automatic for every RMU. |
| Arc-fault pressure relief | Pressure-relief flaps, ducts or a defined exhaust path, depending on enclosure design | Directs hot gases away from accessible areas and reduces enclosure overpressure during an internal fault. | Maintain the required clearance and never obstruct pressure-relief routes. |
| Sealed primary enclosure | Sealed-for-life gas or solid-insulated primary compartment, depending on design | Reduces exposure to dust, humidity and accidental contact with energized primary parts. | Check enclosure integrity, gas-pressure indication where applicable and end-of-life handling requirements. |
| Loss-of-service continuity | Larger RMUs may offer LSC2A or LSC2B classifications, depending on construction | Defines how far adjacent compartments can remain energized during access or maintenance activities. | Confirm the declared LSC classification and the permitted access conditions for each compartment. |
| Partition classification | PM or PI classification, depending on whether partitions are metallic or insulating | Indicates the material and continuity of partitions between functional units and accessible areas. | Review the type-test declaration and ensure the classification meets the system safety philosophy. |
| Cable testing and access | Dedicated cable compartment with screening, shutters or defined test points | Supports voltage testing, phasing and cable maintenance while limiting access to adjacent live parts. | Verify the approved test procedure, voltage-detection method and isolation requirements. |
| Voltage presence indication | Capacitive voltage detection system, commonly designed according to IEC 62271-213 | Provides a visible indication that a circuit may be energized before earthing or cable work. | Use an approved proving unit and never treat indication alone as proof of deadness. |
| Protection and control | Overcurrent, earth-fault, transformer protection and optional remote-control functions | Detects abnormal conditions and reduces fault-clearing time, limiting thermal and mechanical stress. | Coordinate pickup values, time delays, CT performance and breaker operating time with the network study. |
| Environmental protection | Typical indoor enclosures: IP2X or higher for accessible external surfaces; higher IP ratings may apply | Limits accidental contact and protects internal components from solid objects and moisture according to the declared rating. | Confirm the required IP level, ambient temperature, altitude, condensation and pollution conditions. |
| Standards and type testing | IEC 62271-200 for AC metal-enclosed switchgear; IEC 62271-100 for AC circuit breakers; IEC 62271-102 for disconnectors and earthing switches | Provides a recognized basis for dielectric, temperature-rise, short-circuit, mechanical and internal-arc performance. | Request current type-test reports and ensure the tested configuration matches the proposed RMU arrangement. |
| Installation and maintenance safety | Clear operating instructions, mimic diagram, padlocking points, safe access zones and documented maintenance intervals | Converts equipment capability into consistent safe operation throughout the asset life. | Follow local electrical-safety rules, lockout/tagout procedures and the approved switching schedule. |