| 1 | Distribution-Class Metal-Oxide Arrestor | Typically used on medium-voltage systems from approximately 3 kV to 36 kV; select MCOV according to the system grounding and continuous operating voltage. | Utility distribution poles, feeders, capacitor banks, and medium-voltage equipment exposed to direct or induced lightning surges. | IEC 60099-4; IEEE C62.11; local utility specifications. | Install as close as practical to the protected equipment. Keep phase and ground leads short and straight, provide a low-impedance earth connection, and maintain required clearances. | Inspect after major storms and at scheduled intervals. Check for cracks, tracking, contamination, loose connections, corrosion, or thermal-disconnector operation. | De-energize and verify absence of voltage before work. Never use the arrester earth terminal as a normal operating-current return path. |
| 2 | Station-Class Metal-Oxide Arrestor | Commonly applied on high-voltage substations and transmission equipment from approximately 36 kV upward, with ratings selected by system studies. | Power transformers, busbars, generator step-up transformers, cable terminations, and high-value substation assets. | IEC 60099-4; IEEE C62.11; applicable transmission-system requirements. | Mount on a rigid structure with adequate mechanical support. Connect directly to the station grounding grid and minimize the distance between the arrester and transformer or cable terminal. | Use visual inspection, leakage-current monitoring where specified, thermographic inspection, and periodic review of surge-event records. | Follow substation switching, isolation, grounding, and approach-distance procedures. Stored energy and induced voltages may remain after disconnection. |
| 3 | Intermediate-Class Metal-Oxide Arrestor | Typically selected for medium- and high-voltage substations where protection performance is required between distribution and station-class applications. | Industrial substations, feeder entrances, switchgear, motor control centers, and medium-voltage transformer protection. | IEC 60099-4; IEEE C62.11; national electrical installation rules. | Coordinate the rated voltage, MCOV, discharge-current capability, and energy rating with the system fault conditions and insulation-coordination study. | Check housing condition, terminal tightness, grounding continuity, contamination, and signs of moisture ingress during planned outages. | Do not select only by nominal system voltage. Temporary overvoltage, grounding method, and fault-clearing time must also be considered. |
| 4 | Riser-Pole Cable-Termination Arrestor | Commonly used on medium-voltage overhead-to-underground transitions, generally within approximately 3 kV to 36 kV systems. | Protection of underground cables, pole-mounted transformers, ring-main units, and overhead line-to-cable transition points. | IEC 60099-4; IEEE C62.11; utility construction standards. | Install on the overhead side of the cable termination where practical. Use a dedicated, short grounding conductor routed with minimal bends and bond it to the cable shield and station earth as designed. | Inspect for wildlife damage, weathering, contamination, corrosion, cable-screen bonding problems, and physical movement of pole hardware. | Maintain climbing and working clearances. Treat the cable screen and arrester earth as potentially energized until the circuit is isolated and grounded. |
| 5 | Transformer-Integrated Surge Arrestor | Available for distribution and industrial transformers across low-, medium-, and selected high-voltage applications; rating must match the transformer winding and system. | Compact protection for transformer bushings, dry-type transformers, oil-immersed transformers, and packaged substations. | IEC 60099-4 for high-voltage arresters; IEC 60076 for transformers; IEEE C62.11 where applicable. | Install according to the transformer manufacturer’s connection diagram. Ensure correct phase-to-ground arrangement, clearances, enclosure ventilation, and bonding to the transformer tank earth. | Inspect during transformer maintenance. Check arrester condition, terminal torque, enclosure seals, signs of overheating, and any pressure-relief or disconnect indicator. | Confirm that the arrester does not interfere with transformer protection, neutral grounding, or pressure-relief systems. Follow oil-handling and arc-flash procedures. |
| 6 | Low-Voltage Type 1 or Type 2 Surge Protective Device | For AC systems up to 1,000 V; Type 1 devices are used at service entrances where partial lightning current may enter, while Type 2 devices are commonly installed in distribution boards. | Commercial buildings, industrial control panels, residential service equipment, renewable-energy systems, and sensitive electronic loads. | IEC 61643-11; IEC 60364-4-44; UL 1449 or equivalent national requirements. | Install with short conductors, correct upstream overcurrent protection, suitable backup disconnection, and an effective protective-earth connection. Coordinate multiple SPDs by location and protection level. | Check status indicators, remote alarm contacts, terminal tightness, enclosure condition, and replacement records after known surge events. | Verify the system earthing arrangement and maximum continuous operating voltage. A failed indicator or disconnected earth can leave equipment unprotected. |
| 7 | Photovoltaic DC Surge Protective Device | Designed for photovoltaic DC circuits up to the device’s declared maximum continuous DC voltage, commonly selected for 600 V, 1,000 V, or 1,500 V PV systems. | Solar-string combiner boxes, inverter DC inputs, rooftop arrays, ground-mounted PV plants, and long outdoor DC cable runs. | IEC 61643-31; IEC 60364-7-712; UL 1449 or equivalent PV-specific requirements. | Use a PV-rated device with the correct polarity, UCPV rating, short-circuit withstand capability, and enclosure rating. Install near the array and inverter when cable length or risk assessment requires protection at both ends. | Inspect status indicators, cartridge condition, enclosure seals, cable glands, grounding conductors, and evidence of moisture, overheating, or mechanical damage. | PV circuits can remain energized in daylight even after AC isolation. Cover or isolate modules where permitted, use DC-rated disconnects, and follow arc-flash and lockout procedures. |