| Rated current (In) | 125 A at the specified reference temperature; adjustable thermal settings may be available on selected models. | Confirms that the breaker can carry the intended continuous load without nuisance tripping. | Check the derating curve, ambient-temperature reference, enclosure temperature, and conductor size. |
| Number of poles | 2-pole, 3-pole, or 4-pole configurations are commonly offered; 3-pole is widely used for three-phase systems. | Determines which live conductors are disconnected during fault isolation. | Match the pole arrangement to the supply system, neutral-switching requirements, and local wiring rules. |
| Rated operational voltage (Ue) | Common ratings include 400/415 V AC; some product families are rated up to 600 V or 800 V AC. | The breaker must be suitable for the system voltage and insulation coordination. | Verify the exact voltage, frequency, altitude, pollution level, and short-circuit test conditions in the datasheet. |
| Interrupting capacity | Typical 415 V AC options range from approximately 18 kA to 50 kA; higher ratings may be available for heavy-duty applications. | The breaker must safely interrupt the prospective short-circuit current at the installation point. | Compare Icu and Ics values under the same voltage and test standard; do not compare kA figures in isolation. |
| Trip technology | Thermal-magnetic trip units are common; electronic trip units provide more precise long-time, short-time, instantaneous, and sometimes ground-fault protection. | Trip technology affects selectivity, adjustment range, monitoring capability, and total cost. | Choose electronic protection when coordination, measurement, or adjustable settings are required. |
| Standards and conformity | IEC 60947-2 is a common international reference; UL 489 may be required for certain North American installations. | Standards define testing, performance, marking, and verification requirements. | Request the applicable test report, declaration of conformity, certification scope, and complete datasheet. |
| Frequency | Usually 50/60 Hz AC; some models may have separate AC and DC application ratings. | Interrupting and operating performance can change with frequency and current type. | Confirm whether the application is AC or DC and obtain the correct pole-series connection diagram for DC use. |
| Installation method | Fixed-mounted versions are common; plug-in or draw-out arrangements may be available depending on the frame design. | Influences panel layout, maintenance time, safety, and accessory compatibility. | Check terminal orientation, mounting dimensions, front clearance, busbar spacing, and enclosure space. |
| Terminal and conductor compatibility | Often suitable for copper or aluminum conductors when the listed terminal kits and tightening torques are used. | Incorrect terminals or torque can cause overheating, loosening, or insulation damage. | Verify conductor cross-section, lug type, allowable cable material, torque values, and terminal accessories. |
| Environmental suitability | Many indoor products operate around −5 °C to +40 °C without special derating; outdoor, humid, dusty, or high-altitude installations require additional review. | Temperature, moisture, dust, and altitude can affect current capacity and insulation performance. | Ask for derating data above 40 °C, altitude limitations, enclosure IP rating, condensation protection, and storage conditions. |
| Protection and accessories | Common options include auxiliary contacts, alarm contacts, undervoltage releases, shunt trips, motor operators, and door-mounted handles. | Accessories support remote control, status indication, emergency shutdown, and integration with control systems. | Confirm accessory voltage, factory or field installation, wiring terminals, lead time, and compatibility with the selected frame. |
| Indicative unit price | Approximately US$80–US$350 for a basic 125 A thermal-magnetic unit; higher interrupting capacity, electronic trips, accessories, and certified configurations can increase the price substantially. | The lowest purchase price may exclude terminals, releases, testing, certification, freight, or taxes. | Treat this as a planning range only; request a delivered quotation with configuration, quantity, Incoterms, currency, warranty, and taxes clearly stated. |
| Lead time and order quantity | Standard configurations may be available from stock; customized trip units, accessories, or large project quantities commonly require additional production time. | Delivery timing affects project commissioning and spare-parts planning. | Confirm stock status, production lead time, minimum order quantity, packaging, spare availability, and replacement policy. |
| Selection priority for 2026 projects | Correct voltage and pole count, adequate Icu/Ics, verified conformity, suitable trip settings, reliable accessories, and documented service support. | A technically suitable breaker reduces safety risks, downtime, and lifecycle cost. | Compare complete technical configurations rather than headline amperage or unit price alone. |